1. General information
Bartec DEPU Temperature Controller is the complete solution for tubular steam traces heaters-controllers, limiters and power setpoint adjusters all in one unit. It is also possible in potentially explosive areas to adjust parameters. DEPU Temperature Controller with current carrying capacity 25 A can achieve fault-free full wave control. It allows easy output adaptation to heating circuit change.
A complete solution for DEPU tubular steam trace heaters is provided by temperature control, limitation and power setpoint adjustment, all in one unit. DEPU is ATEX-certified and approved for use in potentially explosive areas. All functional units are integrated in a standard casing of aluminum. The connecting lines up to 6 mm² are contacted with cage tension spring clamps. The controller is designed as a two point controller and measures the temperature by means of a Pt 100. The limiter works as an independent system and measures the temperature at the hot spot with its own Pt 100. If the temperature exceeds the limit value the limiter interrupts the heater permanently and a fault signal is given. All fault alarms are indicated by a master fault contact. Resetting can be carried out directly on the unit or externally with a key. The power setpoint adjuster works as a fault-free full wave control by means of a semi-conductor relay. A 7-segment display guarantees good readability of the temperature values of controller and limiter through the viewing plate.
2. Specification of DEPU Temperature Controller
Technical data | |
Enclosure | Standard enclosure of aluminum, grey |
Protection class | IP 65 |
Terminals | Wago cage clamp |
Cable entries | Mains supply line 1 x M25 (M32 opt.), Heating cable/cold end 1 x M20 Fault alarm 1 x M20, Remote reset 1 x M20, Sensor 2 x M16 |
Storage temperature | -30 °C to +70 °C |
Ambient temperature | -20 °C to +40 °C |
Weight | 6kg |
Guidelines | Directive 94/9/EG, NAMUR NE 21,, EN 50020, EN 50019, EN 50028,, EN 50014 |
Electrical data | |
Supply voltage | AC 230 V +10 %/-15 % (50 to 60 Hz) (special voltage 254 V on request) |
Rated current - power set point adjuster | max. 25 A |
Power consumption | no load P = 11 VA, ull load Pmax = 5.7 kVA |
Relay outputs | Master fault control-1 changeover contact, 250 V/5 A |
Measuring input (intrinsically safe) | Pt100 (2 or 3 conductors) |
Measuring range Pt100 | 0 °C to +450 °C |
Resolution/measuring accuracy | 1K |
3. Order code selection table
Ordering information | |
DEPU | 17-8887-2636/2300 |
3-wire Pt100 up to 200 °C | 03-9040-0006 |
3-wire Pt100 up to 400 °C | 03-9040-0016 |
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
Tel: +971558915937
Fax: +971558915956
E-mail:
info@rostockgroup.com
technical@rostockgroup.com
commercial@rostockgroup.com
Get the latest special offers and discount information sent to your email address.
Copyright © Rostock Group Co.,Limited All Rights Reserved. Sitemap