1. General Introduction
The AI895 Analog Input Module can directly interface 2-wire transmitters and with a particular connection it can also interface 4-wire transmitters without losing the HART capability. The AI895 Analog Input Module has 8 channels. The module includes Intrinsic Safety protection components on each channel for connection to process equipment in hazardous areas without the need for additional external devices. Each channel can power and monitor a two-wire process transmitter and HART communication. The input voltage drop of the current input is typically 3 V, PTC included. The transmitter supply for each channel is able to provide at least 15 V at a 20 mA loop current to power Ex certified process transmitters and is limited to 23 mA in overload conditions.
TU890 and TU891 Compact MTU can be used with this module and it enables two wire connections to the process devices without additional terminals. TU890 for Ex applications and TU891 for non Ex applications.
2. Specification of AI895
General info | |
Type | Analog Input |
Signal specification | 4...20 mA |
Article number | 3BSC690086R1 |
Number of channels | 8 |
Signal type | Unipolar single ended |
HART | Yes |
SOE | No |
Redundancy | No |
High Integrity | No |
Intrinsic safety | Yes |
Mechanics | S800 |
Detailed data | |
Resolution | 12 bit |
Isolation | GroupWise isolated from ground |
Under/over range | 1.5 / 22 mA |
Error | Typ. 0.05%, Max. 0.1% |
Temperature drift | Typ. 100 ppm/°C |
Input filter (rise time 0-90%) | 20ms |
Current limiting | Built in current limited transmitter power |
CMRR, 50Hz, 60Hz | >80 dB |
NMRR, 50Hz, 60Hz | >10 dB |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | 4.75 W |
Current consumption +5 V Module bus | Typ. 90 mA, Max. <125 mA |
Current consumption +24 V external | Typ. 270 mA, Max. <370 mA |
Diagnostics | |
Front LED’s | F(ault), R(un), W(arning), Tx (HART communication) |
Supervision | Internal process supply |
Environmental and certification | |
CE mark | Yes |
Electrical safety | IEC 61131-2, cFMus |
Hazardous location | ATEX/IECEx Zone 2 with interface to Zone 0, cFMus C1, Div 2/Zone 2 with interface to C1, C2, C3 Div 1/Zone 0 |
Marine certification | ABS, BV, DNV-GL, LR, RS, CCS |
Protection rating | IP20 according to IEC 60529 |
Corrosive atmosphere ISA-S71.04 | G3 |
Climatic operating conditions | 0 to +55 °C (Storage -25 to +70 °C), RH=5 to 95 % no condensation, IEC/EN61131-2 |
Pollution degree | Degree 2, IEC 60664-1 |
Mechanical operating conditions | IEC/EN 61131-2 |
EMC | EN 61000-6-4 and EN 61000-6-2 |
Overvoltage categories | IEC/EN 60664-1, EN 50178 |
Equipment class | Class I according to IEC 61140; (earth protected) |
Max ambient temperature | 55 °C (131 °F), for vertical mounting 40 °C (104 °F) |
RoHS compliance | DIRECTIVE/2011/65/EU (EN 50581:2012) |
WEEE compliance | DIRECTIVE/2012/19/EU |
Comp ability | |
Use with MTU | TU890, TU891 or TU891Z |
Keying code | AE |
Intrinsic Safety parameters | |
U0 (Groups CENELEC USA) | IIC |
I0 (Groups CENELEC USA) | IIB |
P0 (Groups CENELEC USA) | IIA |
U0 - C0 (uF) | 0.087 |
U0 -L0 (mH) | 4.1 |
U0 -L/R (uH/O) | 55 |
I0 - C0 (uF) | 0.702 |
I0 -L0 (mH) | 16.4 |
I0 -L/R (uH/O) | 222 |
P0 - C0 (uF) | 2.23 |
P0 -L0 (mH) | 32.8 |
P0 -L/R (uH/O) | 443 |
Dimensions | |
Width | 45 mm (1.77”) |
Depth | 102 mm (4.01”), 111 mm (4.37”) including connector |
Height | 119 mm (4.7”) |
Weight | 0.2 0.2 kg (0.44 lbs.) |
3. Selection table of I/O Modules
Name | HART | High Integrity | Intrinsic safety | Mechanics | Redundancy | SOE | Type |
AI801 | No | No | No | S800L | No | No | Analog Input |
AI810 | No | No | No | S800 | No | No | Analog Input |
AI815 | Yes | No | No | S800 | No | No | Analog Input |
AI820 | No | No | No | S800 | No | No | Analog Input |
AI825 | No | No | No | S800 | No | No | Analog Input |
AI830A | No | No | No | S800 | No | No | Analog Input |
AI835A | No | No | No | S800 | No | No | Analog Input |
AI843 | No | No | No | S800 | Yes | No | Analog Input |
AI845 | Yes | No | No | S800 | Yes | No | Analog Input |
AI880A | Yes | Yes | No | S800 | Yes | No | Analog Input |
AI890 | No | No | Yes | S800 | No | No | Analog Input |
AI893 | No | No | Yes | S800 | No | No | Analog Input |
AI895 | Yes | No | Yes | S800 | No | No | Analog Input |
AO801 | No | No | No | S800L | No | No | Analog Output |
AO810V2 | No | No | No | S800 | No | No | Analog Output |
AO815 | Yes | No | No | S800 | No | No | Analog Output |
AO820 | No | No | No | S800 | No | No | Analog Output |
AO845A | Yes | No | No | S800 | Yes | No | Analog Output |
AO890 | No | No | Yes | S800 | No | No | Analog Output |
AO895 | Yes | No | Yes | S800 | No | No | Analog Output |
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
Tel: +971558915937
Fax: +971558915956
E-mail:
info@rostockgroup.com
technical@rostockgroup.com
commercial@rostockgroup.com
Get the latest special offers and discount information sent to your email address.
Copyright © Rostock Group Co.,Limited All Rights Reserved. Sitemap