1. General Introduction
The device converts the signal of a resistance thermometer, thermocouple, or potentiometer to a proportional output current. The device can also be configured as a signal splitter. The removable terminal block K-CJC-** is available as an accessory for internal cold junction compensation of thermocouples. A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error message output. The device is easily configured by the use of the PACTware configuration software. For additional information, refer to the manual .
2. General Specification for KFD2-UT2-2
Model | KFD2-UT2-2 |
General specifications | |
Signal type | Analog input |
Functional safety related parameters | |
Safety Integrity Level (SIL | SIL 2 |
Supply | |
Connection | terminals14+, 15- or power feed module/Power Rail |
Rated voltage Ur | 20 ... 30 V DC |
Ripple | within the supply tolerance |
Rated current Ir | approx. 100 mA |
Power dissipation/power consumption | ≤1.53 W / 1.53 W |
Interface | |
Programming interface | programming socket |
Input | |
Connection side | field side |
Connection | terminals 1, 2, 3, 4, 6 |
RTD | type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995) type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94) type Cu10, Cu50, Cu100 (P50353-92) type Ni100 (DIN 43760 |
Measuring current | approx. 200 A with RTD |
Types of measuring | 2-, 3-wire connection |
Lead resistance | ≤ 50 Ω per line |
Measurement loop monitoring | sensor breakage, |
Thermocouples | type B, E, J, K, N, R, S, T (IEC 584-1: 1995) type L (DIN 43710: 1985) type TXK, TXKH, TXA (P8.585-2001) |
Cold junction compensation | external and internal |
Measurement loop monitoring | sensor breakage |
Potentiometer | 0.8 ... 20 k |
Voltage | 0 ... 20 k(2-wire connection), 0.8 ... 20 k(3-wire connection) |
Input resistance | ≥1 M(-100 ... 100 mV) |
Output | |
Connection side | control side |
Connection | output I: terminal 7: source (-), sink (+), terminal 8: source (+), terminal 9: sink(-) output II: terminal 10: source (-), sink (+), terminal 11: source (+), terminal 12: sink(-) |
Output I, II | 0 ... 20 mA or 4 ... 20 mA |
Current range | 250 V AC / 2 A / cos ≥0.7 ; 40 DC / 2 |
Mechanical life | 5 x 107 switching cycles |
Source | load 0 ... 550 open-circuit voltage ≤18 Vs |
Sink | Voltage across terminals 5 ... 30 V. If the current is supplied from a source > 16.5 V, series resistance of ≥(V - 16.5)/0.0215 is needed, where V is the source voltage. The maximum value of the resistance is (V - 5)/0.0215 . |
Transfer characteristics | |
Deviation | |
After calibration | Pt100: ± (0.06 % of measurement value in K + 0.1 % of span + 0.1 K (4-wire connection)) thermocouple: ± (0.05 % of measurement value in °C + 0.1 % of span + 1 K (1.2 K for types R and S)) this includes ± 0.8 K error of the cold junction compensation mV: ± (50 V + 0.1 % of span) potentiometer: ± (0.05 % of full scale + 0.1 % of span, (excludes errors due to lead resistance)) |
Influence of ambient temperature | deviation of CJC included: Pt100: ± (0.0015 % of measurement value in K + 0.006 % of span)/K Tamb*) thermocouple: ± (0.02 K + 0.005 % of measurement value in °C + 0.006 % of span)/K Tamb*) mV: ± (0.01 % of measurement value + 0.006 % of span)/K Tamb*) potentiometer: ± 0.006 % of span/K Tamb*) *) Tamb = ambient temperature change referenced to 23 °C (296 K) |
Influence of supply voltage | < 0.01 % of span |
Influence of load | ≤0.001 % of output value per 100 |
Reaction time | worst case value (sensor breakage and/or sensor short circuit detection enabled) mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2- wire RTD: 920 ms, Potentiometer: 3-wire connection 2.8 s, 2-wire connection 2.25 s |
Galvanic isolation | |
Input/Other circuits | basic insulation according to IEC 61010-1, rated insulation voltage 300 Veff |
Output/supply, programming input | functional insulation, rated insulation voltage 50 V AC There is no electrical isolation between the programming input and the supply. The programming cable provides galvanic isolation so that ground loops are avoided. |
Indicators/settings | |
Display elements | LEDs display |
Configuration | via PACTware |
Configuration | via operating buttons via PACTware |
Labeling | space for labeling at the front |
Directive conformity | |
Electromagnetic compatibility | |
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity | |
Electromagnetic compatibility | NE 21:2011 |
Degree of protection | IEC 60529:2001 |
Ambient conditions | |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
3. Connection
4. Assembly
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
Tel: +971558915937
Fax: +971558915956
E-mail:
info@rostockgroup.com
technical@rostockgroup.com
commercial@rostockgroup.com
Get the latest special offers and discount information sent to your email address.
Copyright © Rostock Group Co.,Limited All Rights Reserved. Sitemap