1. General Introduction
AFV30D Duplexed Field Control Unit features outstanding processing performance and a large application storage capacity, yet inherits the same quality and stability that are the hallmark of the CENTUM series. It compose of Processor modules CP461/CP471, power supplies PW482/PW481/PW484. Processor modules, power supplies, I/O modules, and communication buses all support redundant configuration. The latest release of the controller has been optimized to take full advantage of advancements in field digital technology that will help plants operate with increased efficiency and stability. A high speed remote I/O unit enables connecting controllers over remote site up to 50 kilometers via optical fiber cables.
2. Standard Specification
Main Characters | Description |
Memory Protection During Power Failure | Battery S9548FA, Back-up for Main Memory: Max. 72 hours, Recharge Time: Min. 48 hours |
READY Contact Output | 2 terminals (NC, C), Contact Points open during FCU failure, Contact Rating: 30 V DC, max. 0.3 A |
Communication Interface | Vnet/IP Interface: Dual-redundant |
No. of Node Units Connectable | Max. 13 of ESB Bus Node Units ANB10 or Optical ESB Bus Node Units ANB11 |
Connection to ESB Bus Node Unit | ESB Bus Coupler Module EC401 or EC402 required. For the dual-redundant configuration of the processor modules, EC401 or EC402 must be installed in both slot 7 and slot 8 . In case ESB Bus has a single configuration, EC401 or EC402 must be installed in slot 7 and keep slot 8 empty. |
Power Supply Module | Voltage: 220-240 V AC, Frequency: 50/60 Hz, PW482; Voltage: 100-120 V AC, Frequency: 50/60 Hz, PW481; Voltage: 24 V DC, PW484. 2 modules for dual-redundant configuration. |
Processor Module | CP461 and CP471(applicable for R6.05 or later version), A dual-redundant configuration is enabled by using 2 identical modules |
I/O Module Slots | Support max. 8 I/O modules |
3. Model Selection of AFV30D Duplexed Field Control Unit
Model | Suffix Codes | Description | ||||||
AFV30D | Duplexed Field Control Unit (for Vnet/IP and FIO, 19-inch Rack Mountable) | |||||||
-A | Standard type (for CP471) | |||||||
-S | Standard type (for CP461) | |||||||
4 | Dual-redundant Vnet/IP, dual-redundant power supply | |||||||
1 | Always 1 | |||||||
1 | 100 - 120 V AC power supply | |||||||
2 | 220 - 240 V AC power supply | |||||||
4 | 24 V DC power supply | |||||||
0 | Basic type | |||||||
1 | With ISA Standard G3 option | |||||||
5 | Basic type with no explosion protection | |||||||
6 | With ISA Standard G3 option and no explosion protection | |||||||
E | Basic type with explosion protection | |||||||
F | With ISA Standard G3 option and explosion protection | |||||||
1 | LFS1700 Control function for field control station( for CP461) | |||||||
2 | Always 2 (R6.01 or later) | |||||||
Option Codes | /HKU | With HKU interface | ||||||
/ATDOC | Explosion Protection Manual | |||||||
/MRN | With Marine Standards |
4.Typical Order Codes
Typical order codes | Remarks |
AFV30D-S41251 | CP461, 220V, Basic, R5 or earlier |
AFV30D-S41252 | CP461, 220V, Basic, R6 |
5. System Configuration
6. External Dimension
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
Tel: +971558915937
Fax: +971558915956
E-mail:
info@rostockgroup.com
technical@rostockgroup.com
commercial@rostockgroup.com
Get the latest special offers and discount information sent to your email address.