1. General Introduction
ANB10S ESB Bus Node Unit has an interface function that communicates the analog I/O signals and contact I/O signals of a field with a Field Control Unit (FCU) via an ESB bus, as well as a function that supplies power to the I/O Modules. This node units are connected to FCU via an ESB bus.
2. Standard Specification
Main Characters | Description |
Connection to Field Control Unit (FCU) | ESB Bus Coupler Module EC401 or EC402 required. For the dual-redundant configuration of the processor modules, EC401 or EC402 must be installed in both slot 7 and slot 8 . In case ESB Bus has a single configuration, EC401 or EC402 must be installed in slot 7 and keep slot 8 empty. |
No. of Node Units Connectable | Max. 13 to AFV30S or AFV30D |
Power Supply Module | Voltage: 220-240 V AC, Frequency: 50/60 Hz, PW482; Voltage: 100-120 V AC, Frequency: 50/60 Hz, PW481; Voltage: 24 V DC, PW484. 2 modules for dual-redundant configuration. |
ESB Bus Interface Slave Module | SB401, Two modules in case of a dual-redundant configuration. |
I/O Module Slots | Support max. 8 I/O modules |
3. Model Selection of ANB10S ESB Bus Node Unit
Model | Suffix Codes | Description | |||
ANB10S | Node Unit for Single ESB Bus | ||||
-3 | Single power supply | ||||
-4 | Dual-redundant power supply | ||||
1 | 100 - 120 V AC power supply | ||||
2 | 220 - 240 V AC power supply | ||||
4 | 24 V DC power supply | ||||
5 | Basic type with no explosion protection | ||||
6 | With ISA Standard G3 option, temperature (-20 ˚C to 70 ˚C) option, and no explosion protection | ||||
7 | With ISA Standard G3 option and no explosion protection | ||||
E | Basic type with explosion protection | ||||
F | With ISA Standard G3 option, temperature (-20 ˚C to 70 ˚C) option, and explosion protection | ||||
G | With ISA Standard G3 option and explosion protection | ||||
Option Codes | /CU1N | Connector Unit for ESB Bus [part No.: S9562FA] | |||
/CU1T | Connector Unit with Terminator for ESB Bus [part No.: S9564FA] | ||||
/ATDOC | Explosion Protection Manual |
4. Typical Order Codes
Typical order codes | Remarks |
ANB10S-325/CU2N | single 220V, Basic & middle node type |
ANB10S-325/CU2T | single 220V, Basic & end node type |
ANB10S-425/CU2N | redundant 220V, Basic & middle node type |
ANB10S-425/CU2T | redundant 220V, Basic & end node type |
5.External Dimension
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
Tel: +971558915937
Fax: +971558915956
E-mail:
info@rostockgroup.com
technical@rostockgroup.com
commercial@rostockgroup.com
Get the latest special offers and discount information sent to your email address.
Copyright © Rostock Group Co.,Limited All Rights Reserved. Sitemap