1. General Introduction
ADV551 Digital output Module can be installed on Field Control Unit or ESB bus node unit for 24VDC Voltage output digital signals to field. Three types of connection selectable as Pressure clamp terminal, MIL connector cable or dedicated cable AKB331, Dual-redundant communication is available by installing two communication modules on the same unit.
2. Standard Specification
Main Characters | Description |
Number of input channels | 32, isolated |
Rated applied voltage | 24 V DC (sink/source) |
External power supply voltage, range | 20.4 to 26.4 V DC |
Output ON voltage maximum value | 2 V DC |
Output format | Current sink |
Maximum load current | 100 mA/channel, 26.4 V |
Withstanding voltage | Between output signal and system: 2 kV AC, For 1 minute Between commons: 500 V AC, For 1 minute, common minus (–) side every 16-channel |
Input response time | 3 ms or less (for status output) 10 ms or less (for mixed status and pulse outputs) |
Pulse width | 8 ms to 7200 s |
Pulse width resolution | 8 ms, but ON/OFF delay of maximum 1 ms is added |
Maximum current consumption | 700 mA (5 V DC), 60 mA (external power supply) |
External connection | Pressure clamp terminal, MIL connector cable, dedicated cable (AKB331) |
3. Model Selection of ADV551 Digital Output Module
Model | Suffix Codes | Description | |||
ADV551 | Digital Output Module (32-channel, 24 V DC, Isolated) | ||||
-P | With pushbutton input | ||||
5 | Without status display; with no explosion protection | ||||
6 | With status display; with no explosion protection | ||||
E | Without status display; with explosion protection | ||||
F | With status display; with explosion protection | ||||
0 | Basic type | ||||
3 | With ISA Standard G3 option and temperature (-20 to 70 °C) option | ||||
Option Code | /D5A00 | With KS Cable Interface Adapter for 32-channel digital [Model: ATD5A-00] | |||
/B5S00 | With Pressure Clamp Terminal Block for Digital Input [Model: ATB5S-00] | ||||
/B5S10 | With Pressure Clamp Terminal Block for Digital Input (surge absorber) [Model: ATB5S-10] | ||||
/B5D00 | With Dual Pressure Clamp Terminal Block for Digital Input [Model: ATB5D-00] | ||||
/B5D10 | With Dual Pressure Clamp Terminal Block for Digital Input (surge absorber) [Model: ATB5D-10] | ||||
/CCC01 | With Connector Cover for MIL Cable [Model: ACCC01] |
4. Typical Order Codes
Typical order codes | Remarks |
ADV551-P50 | Standard type |
ADV551-P60 | Standard type with status display |
ADV551-P53 | Standard type, G3 option and wide temperature (-20 to 70 °C) option |
ADV551-P63 | Standard type with status display, G3 option and wide temperature (-20 to 70 °C) option |
ADV551-P50/D5A00 | Standard type with ATD5A terminal block |
ADV551-P60/D5A00 | Standard type with status display, with ATD5A terminal block |
ADV551-P53/D5A00 | Standard type, G3 option and wide temperature (-20 to 70 °C) option, with ATD5A terminal block |
ADV551-P63/D5A00 | Standard type with status display, G3 option and wide temperature (-20 to 70 °C) option, with ATD5A terminal block |
5.External Dimension
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
Tel: +971558915937
Fax: +971558915956
E-mail:
info@rostockgroup.com
technical@rostockgroup.com
commercial@rostockgroup.com
Get the latest special offers and discount information sent to your email address.
Copyright © Rostock Group Co.,Limited All Rights Reserved. Sitemap