1. General Introduction
Durag D-UG 660 is self-monitoring and fail-safe control unit for monitoring gas, oil and coal flames with DURAG UV, UV+IR or IR-flame sensors, primarily in multi-burner view applications. It analyses the flame radiation via the pulse signal of the flame sensor connected. The easy-to-read LCD display continually shows information on the defined setting and operational status. The flame intensity and signal are present at two current outputs 0/4 ... 20 mA for further analysis. It mainly come with typical features as below:
u Suitable for intermittent operation as well as continuous operation
u Optional parallel operation of two flame sensors in any combination: UV/UV, UV/IR or IR/IR.
u Three different settings supported for various modes: dependent on fuel or combustion technology, automatic activation by burner management system
u Plain text display
2. General Specification
Operation mode | Intermittent operation, continuous operation, 72-hour operation without continual supervision | Pre-configurable combinations of switching threshold and safety time | 3 |
Safety | Self-monitoring and fail-safe | Flame sensor connection | 1 or 2 (parallel) |
Electrical connection | 24/ 48 VDC, 115/ 230 VAC | Display | alpha-numeric LCD display |
Protection | IP00 | Flame intensity | 0/4 ... 20 mA |
Flame relay | 1x switch-over contact, 230 VAC, 2 A | Flame signal | 0/4 ... 20 mA |
Status relay | 1x switch-over contact, 230 VAC, 2 A | Perm. ambient temperature | 20 °C to +60 °C |
Threshold setting | 00 ... 99 | Dimensions | 19” plug-in module, 3 RU, 21 HP |
FFDT (safety time) | 1 ... 5.5 s | Weight | approx. 1 kg |
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
Tel: +971558915937
Fax: +971558915956
E-mail: