1.General Introduction
Honeywell FS20X flame detector is a Multi-Spectrum and UV/Dual IR/VIS Flame Detector with a proven UV solar-blind sensor, exhibits faster false-alarm free response to fires over a wider temperature range and with a much longer detection range compared to conventional UV/IR detectors. The FS20X Flame Detector has a detection range in excess of 200 feet (very high sensitivity setting) for the detection of a one square-foot Heptane reference fire and has a cone of vision greater in volumetric coverage than most UV/IR detectors. This means fewer detectors can be used as compared to other manufacturers’ detectors. The FS20X Flame Detector uses advanced patented algorithms for signal processing and fire and flame analysis is designed to alarm to all types of fires in all industrial environmental conditions. If the detector’s UV signal is degraded due to heavy smoke or a contaminated lens, the FS20X’s patented* WideBand IR™, Near Band IR and Visible sensors will still alarm to fire but at a reduced sensitivity and slower response time.
2.General Specifications
Items | Description |
Field of view | 90° Full 100% Cone of vision, ± 45° from on axis |
Sensitivity | Very High, High, Medium and Low – Switch Selectable |
Response time | 3-5 Seconds to 1 sq. ft. n-Heptane fire at 100 ft. 3-10 Seconds to 1 sq. ft. n-Heptane fire at 200 ft. |
Spectral sensitivity | Ultraviolet: 185 - 260 nanometers Visible: 400 – 700 nanometers Near Band IR: 0.7 – 1.1 microns Wide Band IR: 1.1 – 3.5 microns |
Operating voltage | 24 VDC nominal (18-32 VDC) - Regulated |
Power consumption | Operating: 83mA @ 24 VDC nominal |
Alarm | 133mA @ 24 VDC nominal |
Heater | 155mA – additional Note: Heater will turn on at 0ºF (-17ºC) |
Output relays | Fire Alarm: SPDT (NO / NC) – De-Energized/Energized, Latching/Non-Latching Fault: SPST (NO) – Normally Energized, Latching/Non-Latching Auxiliary: SPDT (NO / NC) – De-Energized/Energized, Latching/Non-Latching Contacts rating: 1 amp @ 24 VDC |
Analog output | 0 - 20mA stepped - source or sink user selectable |
Loop resistance | 50 - 400 Ohms |
Communication | RS-485, ModBus Protocol RS-485, FireBus II RS-485 Special (optional) HART, Optional plug-in module |
Visual indications | Green LED: Power Red LED: Alarm Yellow LED: Fault |
Temperature range | Operating: -40℉to +185℉ (-40℃ to +85℃); Storage: -67℉ to +230℉(-55℃ to +110℃) |
Humidity range | 5 to 98% relative humidity, non-condensing |
Vibration | Meets or exceeds Mil Spec 810C Method 514.2, Curve AW12 |
Wiring | 14 AWG (2.5mm2) to 22 AWG (0.326mm2); Shielded Cable Recommended |
Conduit entries | Standard: Two M25 or two 3/4" NPT |
Enclosure materials | Copper-free powder coated aluminum or 316 stainless steel |
Enclosure type | IP66 and NEMA 4 & 4X |
Certifications | FM, ATEX, CE |
Shipping weight | Aluminum: 1.6 kg (3.6 lbs) Stainless steel: 3.2 kg (7 lbs) |
Mounting | Swivel bracket assembly - optional |
Warranty | Three years from date of shipping |
3.Quick Reference Chart
FS24X-2 | FS24X-9 | FS20X | FS10 | ||
SPECTRALSENSITIVITY | Ultraviolet Band (0.18 - 0.26 μ) | √ | |||
Visible Band (0.4 - 0.7 μ) | √ | √ | √ | √ | |
Near Band IR (0.7 μ – 1.1 μ) | √ | √ | √ | √ | |
Wide Band IR1 (1.1 – 3 μ) | √ | √ | √ | √ | |
Wide Band IR1 (1.1 – 3.5 μ) | √ | ||||
Wide Band IR2 (3.0 – 5.0 μ) | √ | √ | |||
SENSITIVITY(feet) | Very High | 200+ | 200+ | 200+ | 60 |
High | 150 | 150 | 150 | 45 | |
Medium | 100 | 100 | 100 | 30 | |
Low | 50 | 50 | 50 | 15 | |
RESPONSE | Fireball / Quick Response Option (< 500 mS) | √ | |||
Acetylene Long Range Option | √ | ||||
OTHER | Field of View (conical) | 110° | 90° | 90° | 90° |
HART Option | √ | √ | √ | ||
Modbus Built-In | √ | √ | √ | ||
ENCLOSURES | Aluminum Class I, Div._1 | √ | √ | √ | √ |
316 Stainless Steel Class I, Div._1 | √ | √ | √ | √ | |
APPROVALS | FM | √ | √ | √ | √ |
cFM | √ | √ | √ | √ | |
ATEX | √ | √ | √ | √ | |
IECEx | √ | √ | √ | √ | |
INMETRO | √ | √ | √ | ||
GOST-R | √ | √ | √ | ||
SIL 2 Compliant | √ | √ | |||
TEST LAMPS/SOURCE | TL-2055 | √ | √ | √ | |
TL-1055 | √ | √ | √ | ||
FS-846-B | √ | ||||
MOUNT | SM4 bracket | √ | √ | √ | √ |
4.Order Code Selection
Part No. | Description |
FS20X-211 Series, standard temp range -40° to 85°C | |
FS20X-211-21-2 | DUAL IR/UV Detector Copper-Free Aluminum Encl. with (2) 3/4" NPT entries, FM, cFM for Class I, Division 1, Groups A, B, C, D; Class II, Division 1, Groups E, F, G; Class III |
FS20X-211-22-2 | DUAL IR/UV Detector 316 Stainless Steel Encl. with (2) 3/4" NPT entries, FM, cFM for Class I, Division 1, Groups A, B, C, D; Class II, Division 1, Groups E, F, G; Class III |
FS20X-211-23-3 | DUAL IR/UV Detector Copper-Free Aluminum Encl. with (2) M25 entries, FM, cFM, ATEX, IECEx for Class I, Zone 1 |
FS20X-211-24-3 | DUAL IR/UV Detector 316 Stainless Steel Encl. with (2) M25 entries, FM, cFM, ATEX, IECEx for Class I, Zone 1 |
FS20X-211-21-4 | Dual IR/UV Detector Copper-Free Aluminum Encl. with (2) 3/4 in. NPT entries, INMETRO |
FS20X-211-22-4 | Dual IR/UV Detector 316 Stainless Steel Encl. with (2) 3/4 in. NPT entries, INMETRO |
FS20X-211-23-4 | DUAL IR/UV Detector Copper-Free Aluminum Encl. with (2) M25 entries, INMETRO |
FS20X-211-24-4 | DUAL IR/UV Detector 316 Stainless Steel Encl. with (2) M25 entries, INMETRO |
FS20X-212 Series with Hart, standard temp range -40° to 85°C | |
FS20X-212-21-2 | Dual IR/UV copper-free aluminum encl. with (2) 3/4 in. entries, FM/cFM, HART module factory installed |
FS20X-212-22-2 | Dual IR/UV 316 stainless steel encl. with (2) 3/4 in. entries, FM/cFM, HART module factory installed |
FS20X-212-23-3 | Dual IR/UV copper-free aluminum encl. with (2) M25 entries, ATEX/IECEx, HART module factory installed |
FS20X-212-24-3 | Dual IR/UV 316 stainless steel encl. with (2) M25 entries, ATEX/IECEx, HART module factory installed |
FS20X-212-21-4 | Dual IR/UV copper-free aluminum encl. with (2) 3/4 in. NPT entries, INMETRO. HART Module factory installed |
FS20X-212-22-4 | Dual IR/UV stainless steel encl. with (2) 3/4 in. NPT entries, INMETRO. HART Module factory installed |
FS20X-212-23-4 | Dual IR/UV copper-free aluminum encl. with (2) M25 entries, INMETRO, HART module factory installed |
FS20X-212-24-4 | Dual IR/UV 316 stainless steel encl. with (2) M25 entries, INMETRO, HART module factory installed |
Test and Mount accessories | |
FSX-A014 | Optional HART Module for FS20X Detectors |
FVR-01 | Field of View Restrictor |
PSU-12 | Universal charger for Fire Sentry Test Lamps and Interface Kits. For 110-240 VAC with international plugs |
SH-001 | Sunshield for SS2, SS4 & FS24X Detectors, 316 Stainless Steel |
SM4 | Stainless Steel Swivel mounting assembly for FS24X, FS20X, SS4, SS2 detectors |
TL-1055 | IR Test lamp for testing FSX detectors, non-explosion proof version. Including universal charger |
TL-2055 | IR Test lamp for testing FSX detectors, explosion proof version. Including universal charger |
Replacement Detector Module for FS20X | |
FS20X-211-10 | FS20X Replacement Detector Module |
FS20X-212-10 | FS20X Replacement Detector Module w/HART |
Replacement spare parts | |
FSX-A006 | Replacement IR Bulb for TL1055 and TL2055 |
FSX-A011 | Grill Kit for the FS20X |
PW-3123-0005 | Battery Pack for FT-2145/TL-1055/TL-2055 Test Lamp |
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates