1.General Introduction
ABB TSP321 temperature transmitter is a heavy duty modular type sensor with a welded tubular thermowell which is mounted to flange by screw-in thread, terminal box is compression fitting type, sensor can be replaced during operation, transmitter head can be either integrated or remote mounted, both RTD and thermocouple sensors accepted, sensor meets SIL2 approval when integrated with transmitter. Both TTH200 and TTH300 can be integrated; recommend using an LC display with type AS display function if using a TTH200 and LCD indicator with type A if using TTH300.
2.Compare Table of TSP311 TPS321 and TSP311
Type | TSP311 | TSP321 | TSP331 |
Design | No thermowell, for installation in existing thermowell | Welded protective fitting manufactured from pipe material | Drilled thermowell manufactured from bar stock material |
Measuring inset, extension tube with thermowell interface, connection head, transmitter, optional LCD display | |||
Process connection | Insertion in an existing thermowell.
| Screw-in thread, flange, compression fitting | Welded connections, screw-in thread, flange |
Transport temperature / Storage temperature | -20 to 70℃ (-4 to 158 °F) | ||
Maximum temperature limits | (depending on the sensor and material selected, the lower temperature value in each case counts) | ||
Sensor | Thin film resistor: 400℃(752°F), wire wound resistor: 800℃ (1472°F), Thermocouples type K, N, J, E, L, S: 1600℃ (2912°F) | ||
Material | Temperature limits | ||
316L / 1.4404 | ≤ 800℃ (1472°F) | ||
316Ti / 1.4571 | ≤ 800℃ (1472°F) | ||
Inconel 600 / 2.4816 | ≤ 1100℃ (2012°F) | ||
Hastelloy C276 / 2.4819 | — | ≤ 1100℃ (2012°F) | ≤ 1100℃ (2012°F) |
Monel 400 / 2.4360 | — | — | 600℃ (1112°F) |
1.7335 | — | — | ≤ 540℃ (1004°F) |
1.7380 | — | — | ≤ 570℃ (1058°F) |
1.5415 | — | — | ≤ 500℃ (932°F) |
E-CTFE | — | ≤ 120℃ (248°F) | ≤ 120℃ (248°F) |
Tantalum | — | ≤ 250℃ (482°F) | ≤ 250℃ (482°F) |
Pressure | Maximum 40 ... 100 bar (580.15 bar ... 1450.38 psi) | Maximum 700 bar (10152.64 psi) |
3.Basic Code Selection of TSP321 Temperature Transmitter
Main Code | Suffix Codes | Description | |||||||||||
TSP321 | SensyTemp TSP321 Temperature Sensor, with tubular thermowell, for heavy duty applications | ||||||||||||
Explosion Protection / Approvals | Y0 | Without explosion protection | |||||||||||
A1 | Intrinsic Safety ATEX II 1 G Ex ia IIC T6 Ga or II 2 G Ex ib IIC T6 Gb or II 1/2 G Ex ib IIC T6 Ga/Gb | ||||||||||||
A3 | Dust ignition proof ATEX II 1 D IP6x | ||||||||||||
A4 | Dust ignition proof ATEX II 1 D IP6x T133 ... T400 and Intrinsic Safety ATEX II 1 G Ex ia IIC T6 | ||||||||||||
A5 | Flameproof enclosure ATEX II 1/2 G Ex d IIC T1 - T6 Ga/Gb | ||||||||||||
B1 | Non incentive ATEX II 3 G Ex nA IIC T1 - T6 Gc and ATEX II 3 D Ex tc IIIB T133°C Dc | ||||||||||||
B5 | Dust ignition proof ATEX II 1 D IP6x T133 and Flameproof enclosure ATEX II 1/2 G Ex d IIC T6 | ||||||||||||
H1 | Intrinsic Safety IECEx ia IIC T6 Ga | ||||||||||||
H2 | Intrinsic Safety IECEx ib IIC T6 Gb or IECEx ib IIC T6 Ga/Gb | ||||||||||||
H5 | Flameproof enclosure IECEx d IIC T1 - T6 Ga/Gb | ||||||||||||
N1 | Intrinsic Safety acc. NAMUR NE 24 and ATEX II 1 G Ex ia IIC T6 Ga | ||||||||||||
G1 | GOST Russia - metrological approval | ||||||||||||
P2 | GOST Russia - metrological approval and EAC-Ex, Ex i - Zone 0 | ||||||||||||
P3 | GOST Russia - metrological approval and EAC-Ex, Ex d | ||||||||||||
P4 | GOST Russia - metrological approval and EAC-Ex, dust ignition proof | ||||||||||||
G3 | GOST Kazakhstan - metrological approval | ||||||||||||
T2 | GOST Kazakhstan - metrological approval and EAC-Ex, Ex i - Zone 0 | ||||||||||||
T3 | GOST Kazakhstan - metrological approval and EAC-Ex, Ex d | ||||||||||||
T4 | GOST Kazakhstan - metrological approval and EAC-Ex, dust ignition proof | ||||||||||||
M5 | GOST Belarus - metrological approval | ||||||||||||
U2 | GOST Belarus - metrological approval and EAC-Ex, Ex i - Zone 0 | ||||||||||||
U3 | GOST Belarus - metrological approval and EAC-Ex, Ex d | ||||||||||||
U4 | GOST Belarus - metrological approval and EAC-Ex, dust ignition proof | ||||||||||||
Wetted Thermo well Material | S1 | Stainless Steel ASTM 316L (1.4404) | |||||||||||
S2 | Stainless Steel ASTM 316Ti (1.4571) | ||||||||||||
H1 | Highly heat-resistant stainless steel ASTM A446-1 (1.4749) | ||||||||||||
H2 | Heat Resistant Steel 1.4762 | ||||||||||||
H3 | Stainless Steel AISI 314 (1.4841) | ||||||||||||
S9 | Duplex stainless steel (CrNi, 1.4462) | ||||||||||||
S4 | Stainless steel ASTM 904L (CrNi, 1.4539); (Uranus B6) | ||||||||||||
N1 | Ni-Alloy Hastelloy C-276 (2.4819) | ||||||||||||
N2 | Ni-Alloy Hastelloy C-4 (2.4610) | ||||||||||||
N5 | Highly heat-resistant stainless steel , Ni-Alloy Inconel 600 (2.4816) | ||||||||||||
Z9 | Customer specific length | ||||||||||||
Thermowell Type | A1 | Tubular thermowell with straight shaft (DIN 43772, Form 2) | |||||||||||
A2 | Flanged tubular thermowell with straight shaft (DIN 43772, Form 2F) | ||||||||||||
A3 | Screwed tubular thermowell with straight shaft (DIN 43772, Form 2G) | ||||||||||||
B1 | Tubular thermowell, stepped tip (ABB Form 2S) | ||||||||||||
B2 | Flanged tubular thermowell, stepped tip (ABB Form 2FS) | ||||||||||||
B3 | Screwed tubular thermowell, stepped tip (ABB Form 2GS) | ||||||||||||
C1 | Tubular thermowell, tapered (DIN 43772, Form 3) | ||||||||||||
C2 | Flanged tubular thermowell, tapered (DIN 43772, Form 3F) | ||||||||||||
C3 | Screwed tubular thermowell, tapered (DIN 43772, Form 3G) | ||||||||||||
A4 | Screwed tubular thermowell without extension, straight shaft (ABB Form 2G0) | ||||||||||||
B4 | Screwed tubular thermowell without extension, stepped tip (ABB Form 2GS0) | ||||||||||||
B5 | Tubular thermowell d= 22mm, stepped tip d= 6mm | ||||||||||||
K1 | Tubular thermowell, stepped tip 9 mm (0.36 in.) (ABB Form 2S/9) | ||||||||||||
K2 | Flanged tubular thermowell, stepped tip 9 mm (0.36 in.) (ABB Form 2FS/9) | ||||||||||||
K3 | Screwed tubular thermowell, stepped tip 9 mm (0.36 in.) (ABB Form 2GS/9) | ||||||||||||
Z9 | Others | ||||||||||||
Process Connection | Y00 | Without process connection | |||||||||||
A01 | Adjustable compression fitting G 1/2, stainless steel | ||||||||||||
A02 | Adjustable compression fitting 1/2 in. NPT, stainless steel | ||||||||||||
A03 | Adjustable flange DN 25 PN 10 ... PN 40, EN 1092-1 | ||||||||||||
A07 | Adjustable flange 1 in. 150 lbs, ASME B16.5 | ||||||||||||
F01 | Flange DN 15 PN 10 ... PN 40, EN 1092-1 | ||||||||||||
F02 | Flange DN 20 PN 10 ... PN 40, EN 1092-1 | ||||||||||||
F03 | Flange DN 25 PN 10 ... PN 40, EN 1092-1 | ||||||||||||
F29 | Flange DN 25 PN 63 ... PN100, EN 1092-1 | ||||||||||||
F30 | Flange DN 32 PN 16 … PN 40, EN 1092-1 | ||||||||||||
F04 | Flange DN 40 PN 10 ... PN 40, EN 1092-1 | ||||||||||||
F37 | Flange DN 40 PN 63 ... PN 100, EN 1092-1 | ||||||||||||
F06 | Flange DN 50 PN 6, EN 1092-1 | ||||||||||||
F05 | Flange DN 50 PN 10 ... PN 40, EN 1092-1 | ||||||||||||
F33 | Flange DN 50 PN 63, EN 1092-1 | ||||||||||||
F34 | Flange DN 50 PN 100, EN 1092-1 | ||||||||||||
F35 | Flange DN 80 PN 16, EN 1092-1 | ||||||||||||
F36 | Flange DN 100 PN 40, EN 1092-1 | ||||||||||||
F07 | Flange 1 in. 150 lbs, ASME B16.5 | ||||||||||||
F08 | Flange 1 in. 300 lbs, ASME B16.5 | ||||||||||||
F09 | Flange 1 in. 600 lbs, ASME B16.5 | ||||||||||||
F11 | Flange 1-1/2 in. 150 lbs, ASME B16.5 | ||||||||||||
F12 | Flange 1-1/2 in. 300 lbs, ASME B16.5 | ||||||||||||
F13 | Flange 1-1/2 in. 600 lbs, ASME B16.5 | ||||||||||||
F14 | Flange 1-1/2 in. 900 / 1500 lbs, ASME B16.5 | ||||||||||||
F15 | Flange 2 in. 150 lbs, ASME B16.5 | ||||||||||||
F16 | Flange 2 in. 300 lbs, ASME B16.5 | ||||||||||||
F17 | Flange 2 in. 600 lbs, ASME B16.5 | ||||||||||||
F18 | Flange 2 in. 900/1500 lbs, ASME B16.5 | ||||||||||||
S15 | Cylindrical thread G 3/8 A | ||||||||||||
S01 | Cylindrical thread G 1/2 A | ||||||||||||
S02 | Cylindrical thread G 3/4 A | ||||||||||||
S03 | Cylindrical thread G 1 A | ||||||||||||
S07 | Cylindrical thread M20*1.5 | ||||||||||||
S08 | Cylindrical thread M27*2 | ||||||||||||
S04 | Conical thread 1/2 in. NPT | ||||||||||||
S05 | Conical thread 3/4 in. NPT | ||||||||||||
S06 | Conical thread 1 in. NPT | ||||||||||||
S09 | Conical thread 1/2 in. BSPT | ||||||||||||
S10 | Conical thread 3/4 in. BSPT | ||||||||||||
S11 | Conical thread 1 in. BSPT | ||||||||||||
S99 | Others | ||||||||||||
Thermowell Diameter | A9 | 6 mm x 1 mm | |||||||||||
A5 | 8 mm x 2 mm | ||||||||||||
A1 | 9 mm x 1 mm | ||||||||||||
A6 | 10 mm x 1,5 mm | ||||||||||||
A2 | 11 mm x 2 mm | ||||||||||||
A3 | 12 mm x 2,5 mm | ||||||||||||
B6 | 13,5 mm x 2,3 mm | ||||||||||||
B2 | 13,7 mm x 2,24 mm | ||||||||||||
A4 | 14 mm x 2,5 mm | ||||||||||||
A7 | 15 mm x 2 mm | ||||||||||||
A8 | 16 mm x 3 mm | ||||||||||||
B1 | 22 mm x 2 mm | ||||||||||||
Immersion Length | U0 | Without fixed immersion length | |||||||||||
U1 | U = 100 mm (4 in.) | ||||||||||||
U3 | U = 160 mm (6.3 in.) | ||||||||||||
U5 | U = 250 mm (10 in.) | ||||||||||||
U7 | U = 400 mm (16 in.) | ||||||||||||
U9 | Customer specific length | ||||||||||||
Nominal Length | N1 | N = 230 mm (9.1 in.) | |||||||||||
N3 | N = 290 mm (11.42 in.) | ||||||||||||
N5 | N = 380 mm (15 in.) | ||||||||||||
N7 | N = 530 mm (20.9 in.) | ||||||||||||
Z9 | Customer specific length | ||||||||||||
Measuring Inset Type | Y0 | Without measuring inset | |||||||||||
S1 | RTD, TF, Basic application, measuring range -50 ... 400℃ (-58 ... 752°F), 10 g | ||||||||||||
S2 | RTD, TF, Extended vibration resistance, measuring range -50 ... 400℃ (-58 ... 752°F), 60 g | ||||||||||||
S3 | RTD, TF, Extended measuring range -196 ... 400℃ (-321 ... 752°F), 10 g | ||||||||||||
S4 | RTD, TF, Extended vibration resistance, -196 ... 400℃ (-321 ... 752°F), 60 g | ||||||||||||
D1 | RTD, WW, Extended measuring range -196 ... 600℃ (-321 ... 1112°F), 10 g | ||||||||||||
D3 | RTD, WW, Extended vibration resistance, extended measuring range -196 ... 600℃ (-321 ... 1112°F), 60 g | ||||||||||||
E1 | RTD, adjustable to German calibration regulations, sign of app. 000/308 - without calibration | ||||||||||||
E2 | RTD, custody preliminary, adjustable to German regulations, - with calibration -10℃ and +50℃ | ||||||||||||
T1 | Thermocouple | ||||||||||||
Z9 | Others | ||||||||||||
Sensor Type and Wiring | Y0 | Without measuring inset | |||||||||||
P1 | 1 x Pt100, 2-wire | ||||||||||||
P2 | 1 x Pt100, 3-wire | ||||||||||||
P3 | 1 x Pt100, 4-wire | ||||||||||||
P4 | 2 x Pt100, 2-wire | ||||||||||||
P5 | 2 x Pt100, 3-wire | ||||||||||||
P6 | 2 x Pt100, 4-wire | ||||||||||||
P8 | 1 x Pt1000, 2-wire | ||||||||||||
P7 | 1 x Pt1000, 3-wire | ||||||||||||
P9 | 1 x Pt1000, 4-wire | ||||||||||||
K1 | 1 x Type K (NiCr-NiAl) | ||||||||||||
K2 | 2 x Type K (NiCr-NiAl) | ||||||||||||
K3 | 3 x Type K (NiCr-NiAl) | ||||||||||||
J1 | 1 x Type J (Fe-CuNi) | ||||||||||||
J2 | 2 x Type J (Fe-CuNi) | ||||||||||||
L1 | 1 x Type L (Fe-CuNi) | ||||||||||||
L2 | 2 x Type L (Fe-CuNi) | ||||||||||||
N1 | 1 x Type N (NiCrSi-NiSi) | ||||||||||||
N2 | 2 x Type N (NiCrSi-NiSi) | ||||||||||||
T1 | 1 x Type T (Cu-CuNi) | ||||||||||||
T2 | 2 x Type T (Cu-CuNi) | ||||||||||||
E1 | 1 x Type E (NiCr-CuNi) | ||||||||||||
E2 | 2 x Type E (NiCr-CuNi) | ||||||||||||
S1 | 1 x Type S (Pt10Rh-Pt) | ||||||||||||
S2 | 2 x Type S (Pt10Rh-Pt) | ||||||||||||
Z9 | Others | ||||||||||||
Sensor Accuracy | B2 | Accuracy Class B, IEC 60751 | |||||||||||
D2 | Wire Wound, Double, Accuracy Class A, IEC 60751, Range 0 ... 250℃ (32 ... 482°F) | ||||||||||||
D1 | Wire Wound, Accuracy Class A, IEC 60751, Range -100 ... 450℃ (-148 ... 842°F) | ||||||||||||
S1 | Thin Film, Accuracy Class A, IEC 60751, Range -30 ... 300℃ (-22 ... 572°F) | ||||||||||||
S3 | Thin Film, Accuracy Class AA, IEC 60751, Range 0 ... 100℃ (0 ... 212°F) | ||||||||||||
S6 | Thin Film, Accuracy Class A, IEC 60751, Range -196 ... 400℃ (-320,8 ... 752°F) | ||||||||||||
S8 | Thin Film, Accuracy Class AA, IEC 60751, Range -196 ... 400℃ (-320,8 ... 752°F) | ||||||||||||
T2 | Thermocouple, Accuracy Class 2, IEC 60584 | ||||||||||||
T1 | Thermocouple, Accuracy Class 1, IEC 60584 | ||||||||||||
T4 | Thermocouple, Standard Accuracy ANSI MC96.1 | ||||||||||||
T3 | Thermocouple, Special Accuracy ANSI MC96.1 | ||||||||||||
T5 | Thermocouple, Accuracy according to DIN 43710 | ||||||||||||
Z9 | Others | ||||||||||||
Connection Head Type / Material | L1 | AGL / Aluminium, screwed cover | |||||||||||
L2 | AGLH / Aluminium, high cover, screwed | ||||||||||||
L4 | AGLD / Aluminium, screwed cover with display | ||||||||||||
S1 | AGS / Stainless steel, screwed cover | ||||||||||||
S2 | AGSH / Stainless steel, high cover, screwed | ||||||||||||
S4 | AGSD / Stainless steel, screwed cover with display | ||||||||||||
Z9 | Others | ||||||||||||
Transmitter | Y1 | Without transmitter, sensor with ceramic terminal block - spring loaded | |||||||||||
Y2 | Without transmitter, sensor with flying leads and metal plate - spring loaded | ||||||||||||
H4 | TTH300-HART, programmable, output signal 4 ... 20mA, dual input | ||||||||||||
H5 | TTH300-HART, Ex version, programmable, output signal 4 ... 20mA, dual input | ||||||||||||
P6 | TTH300-PA, programmable, output PROFIBUS PA, dual input | ||||||||||||
P7 | TTH300-PA, Ex version, programmable, output PROFIBUS PA, dual input | ||||||||||||
F6 | TTH300-FF, programmable, output FOUNDATION fieldbus H1, dual input | ||||||||||||
F7 | TTH300-FF, Ex version, programmable, output FOUNDATION fieldbus H1, dual input | ||||||||||||
H6 | TTH200-HART, programmable, output signal 4 ... 20mA | ||||||||||||
H7 | TTH200-HART, Ex version, programmable, output signal 4 ... 20mA | ||||||||||||
Optional codes | /Optional codes |
4.Installation for Normal Diameter and Small Diameters
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
Tel: +971558915937
Fax: +971558915956
E-mail:
info@rostockgroup.com
technical@rostockgroup.com
commercial@rostockgroup.com
Get the latest special offers and discount information sent to your email address.
Copyright © Rostock Group Co.,Limited All Rights Reserved. Sitemap