1. General Introduction
Rosemount 3051L Level Transmitter is a fully-integrated and SIL safety certified transmitter for level measurement, combines the performance and capabilities of Rosemount 3051 Transmitters with the reliability and quality of a direct mount seal in one model number. Rosemount 3051L Level Transmitters offer variety of process connections, configurations, and fill fluid types to meet a breadth of level applications.
Capabilities of a Rosemount 3051L Level Transmitter include: Quantify and optimize total system performance (option code QZ); Tuned-system assembly (option code S1); The Loop Integrity Diagnostic continuously monitors the electrical loop to detect changes that compromise the integrity of the transmitted 4-20 mA output signal (Option Code DA0); LOI with straightforward menus and built-in configuration buttons (option code M4).
2. Range & sensor limits
Range | Minimum span | Lower Range Limit (LRL) 3051L Differential | Lower Range Limit (LRL) 3051L Gauge | Upper Range Limit (URL) |
2 | 1.67 inH2O (4,15 mbar) | –250.00 inH2O (–621,60 mbar) | –250.00 inH2O (–621,60 mbar) | 250.00 inH2O (621,60 mbar) |
3 | 6.67 inH2O (16,58 mbar) | –1000.00 inH2O (–2,48 bar) | 0.50 psia (34,47 mbar) | 1000.00 inH2O (2,48 bar) |
4 | 2.00 psi (137,89 mbar) | –300.00 psi (–20,68 bar) | 0.50 psia (34,47 mbar) | 300.00 psi (20,68 bar) |
3. Basic code selection of 3051L level transmitter
Main Code | Suffix Codes | Description | |||||||
3051L | Level transmitter | ||||||||
Pressure range | 2 | –250 to 250 in H2O (–621,60 to 621,60 mbar) | |||||||
3 | –1000 to 1000 in H2O (–2,48 to 2,48 bar) | ||||||||
4 | –300 to 300 psi (–20,68 to 20,68 bar) | ||||||||
Transmitter output | A | 4–20 mA with digital signal based on HART® Protocol | |||||||
F | FOUNDATION™ Fieldbus Protocol | ||||||||
W | PROFIBUS® PA Protocol | ||||||||
X | Wireless | ||||||||
M | Low-power, 1–5 Vdc with digital signal based on HART Protocol | ||||||||
Process connection size, material, extension length (high side) (Process connection size/ Material/ Extension length) | G0 | 2-in./DN 50/A, 316L SST, Flush mount only | |||||||
H0 | 2-in./DN 50, Alloy C-276, Flush mount only | ||||||||
J0 | 2-in./DN 50, Tantalum, Flush mount only | ||||||||
A0 | 3-in./DN 80, 316L SST, Flush mount | ||||||||
A2 | 3-in./DN 80, 316L SST, 2-in./50 mm | ||||||||
A4 | 3-in./DN 80, 316L SST, 4-in./100 mm | ||||||||
A6 | 3-in./DN 80, 316L SST, 6-in./150 mm | ||||||||
B0 | 4-in./DN 100, 316L SST, Flush mount | ||||||||
B2 | 4-in./DN 100, 316L SST, 2-in./50 mm | ||||||||
B4 | 4-in./DN 100, 316L SST, 4-in./100 mm | ||||||||
B6 | 4-in./DN 100, 316L SST, 6-in./150 mm | ||||||||
C0 | 3-in./DN 80, Alloy C-276, Flush mount | ||||||||
C2 | 3-in./DN 80, Alloy C-276, 2-in./50 mm | ||||||||
C4 | 3-in./DN 80, Alloy C-276, 4-in./100 mm | ||||||||
C6 | 3-in./DN 80, Alloy C-276, 6-in./150 mm | ||||||||
D0 | 4-in./DN 100, Alloy C-276, Flush mount | ||||||||
D2 | 4-in./DN 100, Alloy C-276, 2-in./50 mm | ||||||||
D4 | 4-in./DN 100, Alloy C-276, 4-in./100 mm | ||||||||
D6 | 4-in./DN 100, Alloy C-276, 6-in./150 mm | ||||||||
E0 | 3-in./DN 80, Tantalum, Flush mount only | ||||||||
F0 | 4-in./DN 100, Tantalum, Flush mount only | ||||||||
Mounting flange size, rating, material (high side) (Size/Rating/Material) | M | 2-in/ANSI/ASME B16.5 Class 150/CS | |||||||
A | 3-in/ANSI/ASME B16.5 Class 150/CS | ||||||||
B | 4-in/ANSI/ASME B16.5 Class 150/CS | ||||||||
N | 2-in/ANSI/ASME B16.5 Class 300/CS | ||||||||
C | 3-in/ANSI/ASME B16.5 Class 300/CS | ||||||||
D | 4-in/ANSI/ASME B16.5 Class 300/CS | ||||||||
P | 2-in/ANSI/ASME B16.5 Class 600/CS | ||||||||
E | 3-in/ANSI/ASME B16.5 Class 600/CS | ||||||||
X | 2-in/ANSI/ASME B16.5 Class 150/316SST | ||||||||
F | 3-in/ANSI/ASME B16.5 Class 150/316SST | ||||||||
G | 4-in/ANSI/ASME B16.5 Class 150/316SST | ||||||||
Y | 2-in/ANSI/ASME B16.5 Class 300/316SST | ||||||||
H | 3-in/ANSI/ASME B16.5 Class 300/316SST | ||||||||
J | 4-in/ANSI/ASME B16.5 Class 300/316SST | ||||||||
Z | 2-in/ANSI/ASME B16.5 Class 600/316SST | ||||||||
L | 3-in/ANSI/ASME B16.5 Class 600/316SST | ||||||||
Sensor fill fluid | D | Silicone 200, 49 to 401 °F (–45 to 205 °C) | |||||||
F | Silicone 200 for vacuum applications | ||||||||
L | Dow Corning 704 diffusion pump fluid | ||||||||
C | D.C. Silicone 704 for vacuum applications | ||||||||
A | SYLTHERM XLT | ||||||||
H | Inert (halocarbon) | ||||||||
G | Glycerin and water | ||||||||
N | Neobee M-20 | ||||||||
P | Propylene glycol and water | ||||||||
Low pressure side Configuration/Flange Adapter/Diaphragm material/Sensor fill fluid | 11 | Gage/SST/316L SST/Silicone | |||||||
21 | Differential/SST/316L SST/Silicone | ||||||||
22 | Differential/SST/ Alloy C-276/Silicone | ||||||||
2A | Differential/SST/ 316L SST /Inert (halocarbon) | ||||||||
2B | Differential/SST/ Alloy C-276/(halocarbon) | ||||||||
31 | Tuned-system assembly with remote seal/None/SST/316L SST/Silicone | ||||||||
O-ring | A | Glass-filled PTFE | |||||||
Housing material/Conduit entry size | A | Aluminum/½–14 NPT | |||||||
B | Aluminum/M20 x 1.5 | ||||||||
E | Aluminum, ultra low copper/½–14 NPT | ||||||||
F | Aluminum, ultra low copper/M20 x 1.5 | ||||||||
J | SST/½–14 NPT | ||||||||
K | SST/M20 x 1.5 | ||||||||
P | Engineered polymer/No conduit entries | ||||||||
D | Aluminum/G½ | ||||||||
M | SST/ G½ | ||||||||
Optional codes | Optional codes [ As per optional table of 3051C] |
4. Typical mounting & dimensions for 3051L level transmitter
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
Tel: +971558915937
Fax: +971558915956
E-mail:
info@rostockgroup.com
technical@rostockgroup.com
commercial@rostockgroup.com
Get the latest special offers and discount information sent to your email address.
Copyright © Rostock Group Co.,Limited All Rights Reserved. Sitemap