1. General Introduction
The DI830 is a 16 channel 24 V d.c. digital input module for the S800 I/O. The input voltage range is 18 to 30 V d.c. and the input current is 6 mA at 24 V d.c. Each input channel consists of current limiting components, EMC protection components, input state indication LED and optical isolation barrier. The module cyclically performs self-diagnostics. Module diagnostics include:
· Process power supply supervision (results in a module warning, if detected).
· Event queue full.
· Time synchronization missing.
The input signals can be digitally filtered. The filter time can be set in the range 0 to 100 ms, this means that pulses shorter than the filter time are filtered out and pulses longer than specified filter time get through the filter.
2. Specification of DI830
General info | |
Type | Digital Input |
Signal specification | 24 V d.c. |
Article number | 3BSE013210R1 |
Number of channels | 16 |
Signal type | Current sinking |
HART | No |
SOE | Yes |
Redundancy | No |
High Integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Detailed data | |
Input voltage range, "0" | -30..+5 V |
Input voltage range, "1" | 13..30 V |
Input impedance | 3.2 kΩ |
Isolation | GroupWise isolated from ground |
Filter times (digital, selectable) | 0...100 ms |
Current limiting | Sensor power can be current limited by the MTU |
Maximum field cable length | 600 meters (656 yards) |
Event recording accuracy | -0.3 ms...+0.7 ms |
Event recording resolution | 0.4 ms |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | Typ. 2.3 W |
Current consumption +5 V Module bus | Typ. 100 mA, Max 120 mA |
Current consumption +24 V Module bus | 0 |
Current consumption +24 V external | 0 |
Diagnostics | |
Front LED’s | F(ault), R(un), W(arning), Channel 1-16 ("0" or "1") |
Supervision | Process voltage, 1 per group ; Event queue full; Time synchronization missing |
Status indication of supervision | Module Error, Module Warning, Channel error |
Environmental and certification | |
CE mark | Yes |
Electrical safety | IEC 61131-2, UL 508 |
Hazardous location | C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2 |
Marine certification | ABS, BV, DNV-GL, LR, RS, CCS |
Protection rating | IP20 according to IEC 60529 |
Corrosive atmosphere ISA-S71.04 | G3 |
Climatic operating conditions | 0 to +55 °C (Storage -25 to +70 °C), RH=5 to 95 % no condensation, IEC/EN61131-2 |
Pollution degree | Degree 2, IEC 60664-1 |
Mechanical operating conditions | IEC/EN 61131-2 |
EMC | EN 61000-6-4 and EN 61000-6-2 |
Overvoltage categories | IEC/EN 60664-1, EN 50178 |
Equipment class | Class I according to IEC 61140; (earth protected) |
Max ambient temperature | 55 °C (131 °F), for vertical mounting 40 °C (104 °F) |
RoHS compliance | DIRECTIVE/2011/65/EU (EN 50581:2012) |
WEEE compliance | DIRECTIVE/2012/19/EU |
Comp ability | |
Use with MTU | TU810, TU812, TU814, TU818, TU830, TU833, TU838, TU850 |
Keying code | AA |
Dimensions | |
Width | 45 mm (1.77”) |
Depth | 102 mm (4.01”), 111 mm (4.37”) including connector |
Height | 119 mm (4.7”) |
Weight | 0.22 kg (0.48 lbs.) |
3. Selection table of I/O Modules
Name | HART | High Integrity | Intrinsic safety | Mechanics | Redundancy | SOE | Type |
DI801 | No | No | No | S800L | No | No | Digital Input |
DI802 | No | No | No | S800L | No | No | Digital Input |
DI803 | No | No | No | S800L | No | No | Digital Input |
DI810 | No | No | No | S800 | No | No | Digital Input |
DI811 | No | No | No | S800 | No | No | Digital Input |
DI814 | No | No | No | S800 | No | No | Digital Input |
DI818 | No | No | No | S800 | No | No | Digital Input |
DI820 | No | No | No | S800 | No | No | Digital Input |
DI821 | No | No | No | S800 | No | No | Digital Input |
DI825 | No | No | No | S800 | No | Yes | Digital Input |
DI828 | No | No | No | S800 | No | No | Digital Input |
DI830 | No | No | No | S800 | No | Yes | Digital Input |
DI831 | No | No | No | S800 | No | Yes | Digital Input |
DI840 | No | No | No | S800 | Yes | Yes | Digital Input |
DI880 | No | Yes | No | S800 | Yes | Yes | Digital Input |
DI890 | No | No | Yes | S800 | No | No | Digital Input |
DO801 | No | No | No | S800L | No | No | Digital Output |
DO802 | No | No | No | S800L | No | No | Digital Output |
DO810 | No | No | No | S800 | No | No | Digital Output |
DO814 | No | No | No | S800 | No | No | Digital Output |
DO815 | No | No | No | S800 | No | No | Digital Output |
DO818 | No | No | No | S800 | No | No | Digital Output |
DO820 | No | No | No | S800 | No | No | Digital Output |
DO821 | No | No | No | S800 | No | No | Digital Output |
DO828 | No | No | No | S800 | No | No | Digital Output |
DO840 | No | No | No | S800 | Yes | No | Digital Output |
DO880 | No | Yes | No | S800 | Yes | No | Digital Output |
DO890 | No | No | Yes | S800 | No | No | Digital Output |
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates