1. General Introduction
The TU849 is a module termination unit (MTU) for redundant configuration of Optical Module Bus Modem TB840/TB840A.
The MTU is a passive unit having connections for double power supply, one for each modem, a single electrical Module Bus, two TB840/TB840A and a rotary switch for cluster address (1 to 7) setting.
Four mechanical keys, two for each position, are used to configure the MTU for the right types of modules. Each key has six positions, which gives a total number of 36 different configurations. The configurations can be changed with a screwdriver.
The MTU can be mounted on a standard DIN rail. It has a mechanical latch that locks the MTU to the DIN rail. The latch can be locked/unlocked with a screwdriver.
Termination unit TU848 has individual power supply connections and connects TB840/TB840A to redundant I/O. Termination unit TU849 has individual power supply connections and connects TB840/TB840A to non-redundant I/O.
2. Specification of TU849
General info | |
Type | ABB's Module bus |
Article number | 3BSE042560R1 |
Master or slave | Not Applicable |
Line redundancy | Yes |
Hot Swap | No |
Type | Redundant CI840/CI840A, Redundant I/O, Dual Power |
Power input | 24 V d.c. (19.2 - 30 V) |
Mounting | Vertical or Horizontal |
Detailed data | |
Connector | N/A |
24 V consumption typ. | N/A |
Module Bus current distribution | Maximum 5V 1.5 A 24V 1.5 A |
Mechanical Keys | 36 different combinations |
Acceptable wire sizes | Solid: 0.2 - 2.5 mm2 Stranded: 0.2 -2.5 mm2, 24 -12 AWG Recommended torque: 0.5 Nm |
Rated insulation voltage | 50 V |
Dialectic test voltage | 500 V a.c. |
Power dissipation | 2.5W |
Environmental and certification | |
Temperature, Operating | 55° C (131° F) horizontal mounted. 40° C (104° F) vertical mounted |
Temperature, Storage | -25° C (-13° F) to +70° C (158° F) |
Equipment class | Class I according to IEC 60536; (earth protected) |
Ingress protection | IP20 according to IEC 60529 |
CE- marking | Yes |
Electrical Safety | cULus |
Hazardous Location | cULus Hazardous Location Class 1 Zone 2, ATEX Zone 2 |
Marine certificates | ABS, BV, DNV-GL, LR, RS |
RoHS compliance | DIRECTIVE/2011/65/EU (EN 50581:2012) |
WEEE compliance | DIRECTIVE/2012/19/EU |
Dimensions | |
Width | 124 mm (4.88 in.) |
Depth | 47 mm (1.85 in.) |
Height | 186 mm (7.32 in.) including latch |
Weight (including base) | 0.45 kg (0.99 lbs.) |
3. Selection table of S800I/O Communication Modules
Name | Line redundancy | Master or slave | Module redundancy | Protocol |
CI801 | No | Slave | No | PROFIBUS DP-V1 |
CI840A | Yes | Slave | Yes | PROFIBUS DP-V1 |
CI845 | Yes | Slave | Yes | N/A |
TB820V2 | No | Slave | No | ABB's Module bus |
TB825(Multi Mode) | No | Slave | No | ABB's Module bus |
TB826(Single Mode) | No | Slave | No | ABB's Module bus |
TB840 | Yes | Slave | Yes | ABB's Module bus |
TB842 | Yes | Slave | Yes | ABB's Module bus |
TC810 | Yes | - | Yes | N/A |
TU807 | - | Not Applicable | - | ABB's Module bus |
TU840 | Yes | Not Applicable | Yes | ABB's Module bus |
TU841 | Yes | Not Applicable | ABB's Module bus | |
TU846 | Yes | Not Applicable | Yes | PROFIBUS DP-V1 |
TU847 | Not Applicable | Yes | PROFIBUS DP-V1 | |
TU848 | Yes | Not Applicable | Yes | ABB's Module bus |
TU849 | Yes | Not Applicable | - | ABB's Module bus |
TU860 | - | - | - | N/A |
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
Tel: +971558915937
Fax: +971558915956
E-mail:
info@rostockgroup.com
technical@rostockgroup.com
commercial@rostockgroup.com
Get the latest special offers and discount information sent to your email address.
Copyright © Rostock Group Co.,Limited All Rights Reserved. Sitemap