1. General Introduction
TB842 Module Bus Optical Port is a communication interface between the CI801 or CI840/CI840A FCI and the TB820/TB820V2/TB840/TB840A Module Bus Modem of an I/O cluster or ABB drives units via the Optical Module Bus. TB842 connects to CI801 via TB806 and to CI840/CI840A via TU847 and TB806 for single I/O or via TU846 and TB846 for redundant I/O.
TB842 can be used in both a simplex optical configuration as well as in a duplex optical configuration. In a simplex configuration, the optical Module Bus nodes are connected in a ring. In a duplex configuration, the optical Module Bus nodes are connected in a row. TB842 has a connector for fiber optic connections and a connection to the communication interface module.
The module is equipped with Transmitter/Receiver for up to 10 Mbit/s. Both plastic and HCS (Hard Clad Silica) optic fiber with connectors (Agilent’s, former Hewlett-Packard, and Versatile Link) can be used with the TB842.
2. Specification of TB842
General info | |
Protocol | ABB's Module bus |
Article number | 3BSE022464R1 |
Master or slave | Slave |
Line redundancy | Yes |
Module redundancy | Yes |
Hot Swap | Yes |
Used together with HI Controller | No |
Mounting | Vertical or Horizontal |
Detailed data | |
Connector | Agilent’s, former Hewlett-Packard, Versatile Link |
24 V consumption typ. | 20mA |
Module Bus current distribution | Fiber optic interface, one transmits and one receives connection for max. 10 Mbit/s. Wavelength 650 nm |
Power dissipation | 0.5W |
Environmental and certification | |
Temperature, Operating | 55° C (131° F) horizontal mounted. 40° C (104° F) vertical mounted |
Temperature, Storage | -25° C (-13° F) to +70° C (158° F) |
Equipment class | Class I according to IEC 60536; (earth protected) |
Corrosion protection | ISA-S71.04: G3 |
Relative humidity | 5 to 95 % no condensation |
Protection class | IP20 according to EN60529, IEC 529 |
CE- marking | Yes |
Electrical Safety | cULus |
Hazardous Location | cULus Hazardous Location Class1 Zone 2, ATEX Zone 2 |
Marine certificates | ABS, BV, DNV-GL, LR, RS, CCS |
RoHS compliance | DIRECTIVE/2011/65/EU (EN 50581:2012) |
WEEE compliance | DIRECTIVE/2012/19/EU |
Dimensions | |
Width | 56.7 mm (2.23”) |
Depth | 17.6 mm (0.69”) |
Height | 42.3 mm (1.67”) |
Weight (including base) | 90 g (0.20 lbs.) |
3. Selection table of S800I/O Communication Modules
Name | Line redundancy | Master or slave | Module redundancy | Protocol |
CI801 | No | Slave | No | PROFIBUS DP-V1 |
CI840A | Yes | Slave | Yes | PROFIBUS DP-V1 |
CI845 | Yes | Slave | Yes | N/A |
TB820V2 | No | Slave | No | ABB's Module bus |
TB825(Multi Mode) | No | Slave | No | ABB's Module bus |
TB826(Single Mode) | No | Slave | No | ABB's Module bus |
TB840 | Yes | Slave | Yes | ABB's Module bus |
TB842 | Yes | Slave | Yes | ABB's Module bus |
TC810 | Yes | - | Yes | N/A |
TU807 | - | Not Applicable | - | ABB's Module bus |
TU840 | Yes | Not Applicable | Yes | ABB's Module bus |
TU841 | Yes | Not Applicable | ABB's Module bus | |
TU846 | Yes | Not Applicable | Yes | PROFIBUS DP-V1 |
TU847 | Not Applicable | Yes | PROFIBUS DP-V1 | |
TU848 | Yes | Not Applicable | Yes | ABB's Module bus |
TU849 | Yes | Not Applicable | - | ABB's Module bus |
TU860 | - | - | - | N/A |
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates