1. General Introduction
S800 I/O is a comprehensive. Distributed and modular process I/O system that communicates with parent controllers and PLCs over industry-standard field buses. The TB825 Module Bus Optical media converter, converts between plastic opto fiber or HCS fiber with versatile link connectors and glass optical fiber with ST connectors.
The TB825 is built in S800L mechanics and DIN rails mounted. TB825 allows distribution of the optical Module Bus up to 1000 m per cluster in star configurations
2. Specification of TB825
General info | |
Protocol | ABB's Module bus |
Article number | 3BSE036634R1 |
Master or slave | Slave |
Line redundancy | No |
Module redundancy | No |
Hot Swap | No |
Used together with HI Controller | Yes |
Detailed data | |
24 V consumption typ. | 96mA |
Environmental and certification | |
Temperature, Operating | 0 to +55 °C |
Temperature, Storage | -25 to +70 °C |
Pollution degree | Degree 2, IEC 60664-1 |
Relative humidity | 5 to 95 % no condensation |
Protection class | IP20 according to EN60529, IEC 529 |
CE- marking | Yes |
Electrical Safety | IEC 61131-2, UL 508 |
Hazardous Location | C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2 |
Marine certificates | ABS, BV, DNV-GL, LR, RS, CCS |
RoHS compliance | DIRECTIVE/2011/65/EU (EN 50581:2012) |
WEEE compliance | DIRECTIVE/2012/19/EU |
Dimensions | |
Width | 136 mm (5.35 in.) including latch |
Depth | 85.6 mm (3.37 in.) |
Height | 58.5 mm (2.30 in.) |
Weight (including base) | 0.21 kg (0.46 lbs) |
3. Selection table of S800I/O Communication Modules
Name | Line redundancy | Master or slave | Module redundancy | Protocol |
CI801 | No | Slave | No | PROFIBUS DP-V1 |
CI840A | Yes | Slave | Yes | PROFIBUS DP-V1 |
CI845 | Yes | Slave | Yes | N/A |
TB820V2 | No | Slave | No | ABB's Module bus |
TB825(Multi Mode) | No | Slave | No | ABB's Module bus |
TB826(Single Mode) | No | Slave | No | ABB's Module bus |
TB840 | Yes | Slave | Yes | ABB's Module bus |
TB842 | Yes | Slave | Yes | ABB's Module bus |
TC810 | Yes | - | Yes | N/A |
TU807 | - | Not Applicable | - | ABB's Module bus |
TU840 | Yes | Not Applicable | Yes | ABB's Module bus |
TU841 | Yes | Not Applicable | ABB's Module bus | |
TU846 | Yes | Not Applicable | Yes | PROFIBUS DP-V1 |
TU847 | Not Applicable | Yes | PROFIBUS DP-V1 | |
TU848 | Yes | Not Applicable | Yes | ABB's Module bus |
TU849 | Yes | Not Applicable | - | ABB's Module bus |
TU860 | - | - | - | N/A |
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates