1. General Introduction
If there is a need to have access to FF process variables in the AC 800M controller, connectivity between the HSE subnet and the controller is established with the CI860 - the Communication Interface FOUNDATION Field bus HSE.
Then FOUNDATION Field bus process data on HSE can be accessed from the IEC 61131 applications in the AC 800M controllers. For this purpose, the CI860 module maps the value and status parts of the FF signals to the IEC 61131 application and vice versa.
The CI860 is powered by the processor unit, via the CEX-Bus, and therefore does not require any additional external power source
2. Specification of CI860
General info | |
Protocol | FOUNDATION Field bus HSE |
Article number | 3BSE032444R1 |
Master or slave | Master /Slave |
Transmission speed | 10/100 Mbit/s |
Line redundancy | No |
Module redundancy | Yes |
Hot Swap | Yes |
Used together with HI Controller | No |
Detailed data | |
Max units on CEX bus | 12 |
Connector | RJ-45 female (8-pin) |
24 V consumption typ. | Typ100 mA |
Environmental and certification | |
Temperature, Operating | 55 °C |
Protection class | IP20 according to EN60529, IEC 529 |
CE- marking | Yes |
RoHS compliance | DIRECTIVE/2011/65/EU (EN 50581:2012) |
WEEE compliance | DIRECTIVE/2012/19/EU |
Dimensions | |
Width | 185 mm (7.3 in.) |
Depth | 59 mm (2.3 in.) |
Height | 127.5 mm (5.0 in.) |
Weight (including base) | 700 g (1.5 lbs) |
3. Selection table of AC800M Communication Modules
Name | Line redundancy | Master or slave | Module redundancy | protocol |
CI853 | Yes | Master / Slave | Yes | COMLI and MODBUS RTU |
CI854A Classic | Yes | Master | Yes | PROFIBUS DP-V1 |
CI854B | Yes | Master | Yes | PROFIBUS DP-V1 |
CI855 | No | Master | No | ABB's Master Bus 300 |
CI856 | No | Master | No | ABB's S100 I/O |
CI857 | No | Master | No | ABB's INSUM |
CI858 | No | Master | No | ABB's Drive Bus |
CI860 | No | Master/ Slave | Yes | FOUNDATION Field bus HSE |
CI862 Classic | No | Master | Yes | ABB's TRIO/Genius I/O |
CI865 | No | Master | No | ABB's Satt I/O |
CI867 | No | Master/ Slave | Yes | MODBUS TCP |
CI868 | No | Master/ Slave | No | IEC 61850 |
CI869 | Yes | Slave | Yes | ABB's Advant Field bus 100 |
CI871 | No | Master | Yes | PROFINET IO |
CI873 | No | Master | Yes | Ethernet IP / Device Net |
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
Tel: +971558915937
Fax: +971558915956
E-mail:
info@rostockgroup.com
technical@rostockgroup.com
commercial@rostockgroup.com
Get the latest special offers and discount information sent to your email address.
Copyright © Rostock Group Co.,Limited All Rights Reserved. Sitemap